Infrared Temperature Sensor |
|
|
|
|
RD-715-HA
|
RDP-24
|
|
RD-715-HA |
|
|
|
|
|
- |
Non-contact temperature measurement |
- |
Quick response time: 14 ms (90 % response) |
- |
Compact and sturdy sensing head |
- |
Temperature range: 0 to 500 |
- |
Drip-proof/Dust-proof IP65 |
- |
CE mark certified |
・Model
・Dimensions
・Spec |
|
Model |
Field-of-View |
Temperature Range |
Output |
RD-715-HA |
15:1 |
0 to 500 |
Direct current 4 to 20 mA DC (2-wire type) |
|
|
|
Sensing Head (Scale: mm) |
|
Electronics (Scale: mm) |
|
Cable End (Scale: mm) |
|
Accessory Sold Separately: Mounting bracket (TFB) (Scale: mm) |
|
Accessory Sold Separately: Air purge collar (ASAP) (Scale: mm) |
|
|
|
|
|
Rating |
Temperature range |
0 to 500 |
Supply voltage |
2-wire type 5 to 30 V DC, 4 to 20 mA
External shunt resistor: Max 1000 |
|
General Structure |
External dimensions |
Sensing head: 14 x 31 mm (diameter x length), M12 x 1
Electronics: 35 x 12 mm |
Mounting |
Fixed, using a mounting bracket (The mounting bracket is sold separately.) |
Material |
Sensing head: Stainless steel
Cable (Sensing head - Electronics): FEP, Cable diameter: 2.8 mm
Cable (Electronics - Cable end): PVC, Cable diameter: 4.3 mm |
Drip-proof/ Dust-proof |
IP65 |
Cable length |
6 m (Sensing head - Electronics: 3 m, Electronics - Cable end: 3 m) |
|
|
Performance |
System accuracy (*1) |
1 % of temperature span |
Spectral range |
8 to 14 m |
Field of view |
15:1 |
Repeatability(*1) |
0.75 % of temperature span |
Temperature coefficient (*2) |
0.05 %/ |
Temperature resolution |
0.1 |
Response time |
14 ms (90 % response) |
Warm-up time |
10 minutes |
Emissivity |
Fixed at 0.950
0.200 to 1.000 [When digital indicating controller (ACS-13A-x/A, sold separately) is used] |
Transmissivity |
Fixed at 1.000 |
(*1) Ambient temperature 235
(*2) Ambient temperature (sensing head) is lower than 18 , and higher than 28 . |
Output |
Analog output |
Direct current 4 to 20 mA DC
Load impedance (loop impedance): 1000 or less |
|
|
Other |
Ambient temperature |
Sensing head: -20 to 120
Electronics: -20 to 80 |
Storage temperature |
-40 to 85 |
Ambient humidity |
10 to 95 %RH (Non-condensing) |
Vibration (sensing head) |
IEC 68-2-6: 3 G, 11-200 Hz, x,y,z directional |
Shock (sensing head |
IEC 68-2-27: 50 G, 11 ms, x,y,z directional |
Weight |
152 g |
Accessories included |
Instruction manual: 1 copy
Nut: 1 piece |
Accessories sold separately |
Mounting bracket (TFB) (Scale: mm)
Air purge collar (ASAP)
Digital indicating controller (ACS-13A-x/A)
Power supply for the RD series (RDP-24)
|
|
|
|