Shinko SHINKO TECHNOS CO.,LTD.
취급제품 고객지원/다운로드 회사소개 문의  
일본어
영어
Temperature & Programble Controllers Indicators Communication Converters Recorders Portable Indicator Input Devices Output Devices
HOME > Temperature Controllers, Programmable Controllers > Digital Temperature Indicating Controllers BCS3
취급제품
온도제어 관련・주변기기
지시조절계・온도조절계
프로그램 컨트롤러
디지털 지시계
통신변환기
기록계
휴대형 지시계
센서・검출단
SSR・전력조절기
신호변환기
수질관리 제품
 
CE 마킹적합품
UL 취득제품
생산종료제품
이용조건
개인정보보호 관련
품질 및 환경활동
Digital Temperature Indicating Controllers
BCS3 Catalog
BCS3 Instruction Manual
 
BCS3  

NEW
Digital Temperature Indicating Controllers BCS3
- The New Basic Model
- 4-Digit LED Display
- Large Key Switch
- Thermocouples(K,J),RTD(Pt100) Multi-Input or Thermocouples (R,S,T) Multi-Input
- Relay Contact or Non-Contact Voltage Output
- Event Output 2 Points(OPTION)
- Dustproof and Waterproof Specifications(Front IP65 Structure)(OPTION)
Model Name
Specifications
Terminal Arrangement
Dimensions
 



The New Basic Model
The BCS3 is a new basic model that compactly combines all the functions required for a temperature controller.
- Simple Design for Easy Operation Settings
- Compact Design Packed with Features
 
to top


High-visibility characters (H12 x W6mm)
We are enhancing visibility by increasing the display font size.
BCS3_Display 
to top


Easy-to-Operate Key Switch Design
We have achieved a design that emphasizes the placement of keys and ease of pressing. By simplifying the setup options, it becomes easy to change settings quickly.
1 When selecting model MOO, it corresponds to thermocouples (K, J), while selecting MOl corresponds to thermocouples
BCS3_Key switch
to top


Thermocouples(K,J),RTD(Pt100) Multi-Input or Thermocouples (R,S,T) Multi-Input
Thermocouples are used in various applications, including industrial uses, because they exhibit stable performance even in high and low temperature environments. BCS3 is a basic model that supports five types of thermocouples: K, J, R, S, and T(*1)
(*1) When selecting model MOO, it corresponds to thermocouples (K, J), while selecting MOl corresponds to thermocouples
Industrial uses image
to top

Relay Contact or Non-Contact Voltage Output
ou can choose between control outputs: relay outputs with contact points and non-contact voltage outputs for SSR driving. Please specify your preference when placing your order according to your application.  
to top

Event Output 2 Points
By adding an option, you can use up to a total of 2 event outputs.  
to top

Dustproof and Waterproof Specifications(Front IP65 Structure)
IP65 structure for dust and water resistance Adopted to withstand harsh environments where dust and water exposure may occur.
to top

Model Name
BCS3_Model Name

to top


Specifications
Rated Scale
Input Input Range Resolution
M00 K -200~1370 -320~2500 1 ()
J -200~1000 -320~1800 1 ()
Pt100 -199.9~850.0 -199.9~999.9

0.1 ()

M01 R 0~1760 0~3200 1 ()
S 0~1760 0~3200 1 ()
T -199.9~400.0 -199.9~750.0 0.1 ()

Input
Thermocouple K.J.R.S.T
(External resistance: 1 000 or less)
RTD Pt100,3-wire type
(Allowable input lead wire resistance: 100 or less per wire)

Power Supply Voltage 100 to 240V AC 50/60Hz
Allowable Voltage Fluctuation Range 85 to 264V AC

External Dimensions W48XH48XD68 (Depth of control panel interior. 60) mm
Mounting Flush
Case Flame-resistant resin (color: Black)
Panel Membrane sheet

Accuracy
Thermocouple

Within士0.3% of each input span士1 digit.
For temperature below 0(32),within土0.4% of input span士1 digit.
However, for R, S input ranging from 0 to 200(32 to 392),the tolerance is within士8(46)

RTD Within土0.2% of input span士1 digit.

Input Sampling Period 500 ms

Control Action PID control (with Auto-Tuning Function)
Pl control: When Derivative Time Setting is Set to 0
PD control (with Auto-Reset Function): When Integral Time Setting is Set to 0
P control(with Auto-Reset Function): When Both Integral Time and Derivative Time Settings are Set to 0
ON/OFF control: When Proportional Band Setting is Set to 0
Proportional Band (P) 0 to 1000 or 2000(Factory default at 10).
Setting it to 0 activates ON/OFF control.
If the input includes decimals, the range is 0.0 to 999.9 or 0.0 to 999.9.
Setting it to 0.0 also activates ON/OFF control.
Integral time(I) 0 to 1000 seconds(Setting it to 0 disables integral action)(Factory default: 200 seconds).
Derivative time(D) 0 to 300 seconds(Setting it to 0 disables derivative action)(Factory default: 50 seconds).
OUT proportional cycle 1 to 120 seconds(Factory default: 30 sec for Relay contact. 3 sec for non-contact voltage).
ON/OFF hysteresis 0.1 to 100.0 ()(Factory default: 1.0).
Output high limit, low limit 0 to 100 %(Not applicable during ON/OFF control) (Factory defaults: Output low limit 0%, Output high limit 100%).

Control Output
Relay contact 1a Control capacity: 3A 250V AC (resistive load).
1A 250V AC (inductive load.cosCl>=0.4).
Electrical lifespan: 100,000 cycles.
Non-contact voltage
(for SSR drive)
10+3V DC
maximum 20mA DC


Insulation Resistance 500V DC 10M or more
Dielectric Strength Between input terminal and power terminal· 1.5kV AC for 1 minute
Between output terminal and power terminal: 1.SkV AC for 1 minute

Power Consumption Approximately 8VA
Ambient Temperature -10~55
Ambient Humidity 35~85%RH(non-condensing)
Weight Approximately 94g
Environmental Specifications RoHS directive compliant

Attached Functions Sensor correction, Set value lock, LED Display Area Selection, Power Failure Countermeasures, Self-Diagnosis, Automatic Cold Junction Temperature Compensation, Burnout Detection(Over-Scale), lndication range and Control Range, Warm-up indication

Options
Event Output
(Alarm Output 2 Points)
Relay contact 1a.
Control capacity: 3A 250V AC (resistive load).
Electrical life: 100.000 cycles.
Loop Abnormal Alarm Detects Abnormalities at the Control End, such as Heater Disconnection or Sensor Disconnection.
Dustproof and Waterproof Front Panel IP65



Included Accessories

Mounting frame(1 piece), User manual(1 copy), Gasket A(1 piece, for optional dustproof and waterproof addition)

Accessories Sold Separately Terminal cover

to top

Terminal Arrangement
 
BCS3_Terminal Arrangement
to top

Dimensions
  Dimensions (Scale: mm)
  BCS3_Dimensions
  Panel cutout(Scale: mm)


BCS3_Panel cutout
to top


CE마킹적합품 / UL취득제품 | 생산종료제품
사이트맵 | 이용조건 | 개인정보보호 관련 | 품질 및 환경활동