Programmable Controller
PCA1 Catalog
PCA1 Instruction Manual
PCA1 Communication Instruction Manual
PCA1  

PCA1 Photo
- Program capacity with 16-patterns, 16-steps
- Easily legible LCD display with 11-segment characters
- Efficient Console software
- Easy-viewing data via Monitoring software
- Enhanced serial communication function
- Drip-proof/Dust-proof structure
- Dimensions
- Spec


Program capacity with 16-patterns, 16-steps
Program capacity: 16-patterns, 16-steps Program control of up to 256 steps is possible by linking patterns.
Program capacity with 16-patterns, 16-steps
to top


Easily legible LCD display with 11-segment characters
11-segment character LCD display is used, so characters can be read easily.
Comparing 7-segment and 11-segment
  
Industry-leading premium display

PV Display: 24.0 x 11.0 mm (H x W)
SV/MV/TIME Display: 14.0 x 7.0 mm (H x W)
PCA1 and PC-900 comparison
PCA1 Display PCA1
PC-900 Display PC-900
  
PV color changes linked with alarm

PV color changes: Orange, Green, Red, When any alarm is ON: Green --> Red, When any alarm is ON: Orange --> Red, or PV color changes by deviation between PV and SV.
Errors can be also checked via action indicators.
PV color changes linked with alarm
Backlight indication time

By setting backlight time (from no operation status until backlight is switched off), displays can be turned off, resulting in energy savings.
 
to top


Efficient Console software
Console software (SWC-PCA101M) is available for data monitoring, editing, loading, etc.
Power to the PCA1 is not required if USB communication cable (CMB-001) is used.
Connecting the PCA1 to a PC using the USB communication cable (sold separately)
to top


Easy-viewing data via Monitoring software
By using the Monitoring software (SWM-PCA101M), setting item change, data logging and monitoring can be carried out on a PC.
PCA1 Monitoring software(SWM-PCA101M)_display
to top

Enhanced serial communication function
Communication protocol: Shinko protocol, Modbus ASCII , and Modbus RTU Modbus ASCII, Modbus RTU: A maximum of 100 pieces of multiple data Read/Write is possible.  
to top

Drip-proof/Dust-proof structure
IP66 (for front panel only), usable in harsh environments where dust is present or water splashes.  
to top

Dimensions
  PCA1 External dimensions
to top



Spec
Input
Input
Thermocouple K, J, R, S, B, E, T, N, PL-II, C(W/Re5-26)
External resistance: 100  max.
However, B input: External resistance: 40  max.
RTD Pt100, JPt100 3-wire type
Allowable input lead wire resistance: 10  max. per wire
However, Pt100, -100.0 to 100.0 : 5  max. per wire
Direct current 0 - 20 mA DC, 4 - 20 mA DC
Input impedance: 50 
Allowable input current: 100 mA max.
DC voltage 0 - 10 mV DC, -10 - 10 mV DC, 0 - 50 mV DC,
0 - 100 mV DC, 0 - 1 V DC:
Input impedance: 1 M min.
Allowable input voltage: 5 V DC max.
Allowable signal source resistance: 2 k max. (0 - 1 V DC)
200  max. (0 - 100 mV DC, 0 - 50 mV DC)
40  max. (-10 - 10 mV DC)
20  max. (0 - 10 mV DC)
0 - 5 V DC, 1 - 5 V DC, 0 - 10 V DC
Input impedance: 100 k min.
Allowable input voltage: 15 V DC max.
Allowable signal source resistance: 100  max.

Output
Control output
Relay contact
1a1b
Control capacity: 3 A 250 V AC (resistive load)
1 A 250 V AC (Inductive load cos=0.4)
Electrical life: 100,000 cycles
Non-contact voltage
(For SSR drive)
12 V DC15%
Max 40 mA (Short circuit protected)
Direct current

4 to 20 mA DC
Resolution: 12000
Load resistance: Max 600 


Event output
EV1 - EV4
Relay contact
1a
Control capacity: 3 A 250 V AC (resistive load)
1 A 250 V AC (inductive load cos=0.4)
Electrical life: 100,000 cycles
Event output EV3, EV4 share one common terminal.


Performance
Reference accuracy
Thermocouple

Within 0.2% of each input span1 digit
However, R, S input 0 to 200 (32 to 392): Within 6 (12)
B input, 0 to 300 (0 to 572): Accuracy is not guaranteed.
K, J, E, T, N input, Less than 0 (32): Within 0.4% of input span1 digit

RTD Within 0.1% of each input span1 digit
Direct current,
DC voltage
Within 0.2% of each input span1 digit

Cold junction compensation accuracy

Within 1, at 0 to 50
Input sampling period 125 ms
Time indication accuracy 0.1% of setting time
Setting accuracy Based on Reference accuracy and Cold junction compensation accuracy
Time setting accuracy 0.1% of setting time
Setting resolution
Temperature Thermocouple, RTD input without decimal point:
 1 ()
Thermocouple, RTD input with decimal point:
 0.1 ()
DC voltage, current input: 1
Time 1 minute or 1 second
Program Performance
Number of patterns 16 (Linkable)
Number of steps 256 (16 steps/pattern)
Repetitions 0 to 9999 times (Repetitions disabled when set to 0.)
Program time range 0 to 99 hours 59 minutes/step, or 0 to 99 minutes 59 seconds/step
(When ----- is set, Fixed value control is performed using step SV.)
Wait value Thermocouple, RTD input without decimal point:
(0 to 100) ()
Thermocouple, RTD input with decimal point:
(0.0 to 100.0) ()
DC voltage, current input:
(0 to 1000) (The placement of the decimal point follows the selection.)
(The Wait action is disabled when set to 0 or 0.0.)